Pellet boiler PE1e Pellet 45 kW to 60 kW / 2 x PE1e / Condensing Heat Exchanger
Get in touch for a Quote - Contact us
Fully automated pellet boiler with induced draft fan and modulating fuel feed.For combustion of 6mm wood pellets according EN ISO 17225, part 2: wood pellet class A1 / D06.
- Retort complete with optimized silicon carbide combustion chamber Including special alloyed two-part combustion grate, consisting from fixed slip-on grate and automatic 110° tilting grate
- Three-way heat exchanger, fully automaticheat exchanger cleaning in the second and third train
- Automatic ash discharge from retort and heat exchanger in 2 separated mobile ash boxes
- Flue gas recirculation FGR
- Automatic ignition by silent ceramic igniter
- Variable speed high efficiency EC induced draft fan
- Double protection system for maximum burn back protection
- Vacuum-controlled combustion with sensorless ember bed monitoring
- Fixed built-in temperature control with HE pump, mixer, shut-off and balancing valve
- External suction modul fitted in the return line in any position
- Room air-independent operation possible
- Scrub and cleaning device set
optional:
- installable electrostatic particle filter
- connection set for room air-independent operation
- flue gas pipe connection at the back
- ash discharge
Control system H 3200 Touch
Microprocessor controls for optimising the combustion process through precise control of the boiler- and exhaust gas temperature, including actuators for primary and secondary air dampers, 7 ” color display for the representation of all important values and status messages with USB interface for updates; including lambdacontrol
Scope of delivery:
- Core module
- 2 mixing heating circuits (outside sensor included) and
- 1 speed-controlled pump output or change-over valve
- Hydraulic module
- 2 speed-controlled outputs for pumps or switching valve
- 6 sensor inputs
- Outside sensor
- Contact probe for 1 mixing heating circuit (2nd heating circuit possible via additional sensor)
Technical data PE1e Pellet |
45 |
50 |
55 |
60 |
L1 Boiler length |
1400 |
1400 |
1400 |
1400 |
L2 Total length |
1490 |
1490 |
1490 |
1490 |
L* Smallest overall length for transport into the boiler room (disassembled, without cover) |
1010 |
1010 |
1010 |
1010 |
B1 Boiler width |
730 |
730 |
730 |
730 |
B2 Boiler width incl. cover for electrostatic particle separator (optional) |
810 |
810 |
810 |
810 |
B3 Distance of flow/return connection from side of boiler |
590 |
590 |
590 |
590 |
B4 Distance between flue gas pipe connection and side of boiler |
395 |
395 |
395 |
395 |
B5 Distance of supply air connection to side of boiler (optional) |
620 |
620 |
620 |
620 |
B6 Clearance from rear flue gas pipe connection to side of boiler (optional) |
150 |
150 |
150 |
150 |
H1 Boiler height |
1620 |
1620 |
1620 |
1620 |
H2 Overall height |
1675 |
1675 |
1675 |
1675 |
H3 Height, flow connection |
1425 |
1425 |
1425 |
1425 |
H4 Height, return connection |
1175 |
1175 |
1175 |
1175 |
H5 Height of rear flue gas pipe connection (optional) |
1090 |
1090 |
1090 |
1090 |
H6 Höhe Anschluss Zuluft (optional) |
100 |
100 |
100 |
100 |
All information in mm!
Performance data PE1e Pellet |
|
45 |
50 |
55 |
60 |
|
Nominal heat output |
kW |
45 |
50 |
55 |
60 |
|
Output range |
kW |
13,5 - 45 |
15 - 50 |
16,5 - 55 |
18 - 60 |
|
Energy efficiency class of the boiler 1) |
|
|
|
|
|
|
Electrical connection 230V / 50Hz / fused C16A |
||||||
Power consumption at NL / PL |
W |
65 / 30 |
68 / - |
|
72 / - |
75 / - |
Boiler weight (without water content) |
kg |
650 |
650 |
|
650 |
650 |
Total boiler capacity (water) |
liter |
113 |
113 |
|
113 |
113 |
Pellet container capacity |
liter |
170 |
170 |
|
170 |
170 |
Ash box capacity combution camber / heat exchanger |
liter |
37 / 12 |
37 / 12 |
|
37 / 12 |
37 / 12 |
Available feed height of the pump 2) (at ΔT = 20K) |
mbar |
560 |
500 |
|
430 |
380 |
Max. permitted operating temperature |
bar |
|
|
90 |
|
|
Permitted operating pressure |
bar |
|
|
3 |
|
|
Boiler class as per EN 303-5: 2012 |
|
|
|
5 |
|
|
Airborne sound level |
dB(A) |
|
|
< 70 |
|
|
|
|
|
|
|
|
|
Permitted fuel as per EN ISO 17225 3) Recommended tank capacity approx |
liter |
P 1500 |
art 2: Wood pellets class A1 / D06 1500 1500 1500 |
|||
Boiler data for sizing the flue gas system |
|
45 |
50 |
55 |
60 |
|
Flue gas temperature NL / PL |
°C |
140 / 90 |
145 / 90 |
150 / 95 |
160 / 95 |
|
Flue gas mass flow NL / PL |
kg/h |
100 / 33 |
107 / 34 |
118 / 37 |
120 / 40 |
|
Flue gas mass flow NL / PL |
kg/s |
0,028 / 0,009 |
0,03 / 0,009 |
0,033 / 0,010 |
0,034 / 0,011 |
|
Co2 volume concentration NL / PL |
% |
11,8 / 10,3 |
12,3 / 10,3 |
12,3 / 11,3 |
13,3 / 11,3 |
|
Co2 volume concentration NL / PL |
% |
8,5 / 10,0 |
8,0 / 10,0 |
8,0 / 9,0 |
7,0 / 9,0 |
|
Required feed pressure NL / PL |
Pa |
5 / 2 |
5 / 2 |
5 / 2 |
5 / 2 |
|
Required feed pressure NL / PL |
mbar |
0,05 / 0,02 |
0,05 / 0,02 |
0,05 / 0,02 |
0,05 / 0,02 |
|
Maximum feed pressure |
Pa / mbar |
30,0 / 0,3 |
30,0 / 0,3 |
30,0 / 0,3 |
30,0 / 0,3 |
|
Maximum permitted suction resistance |
Pa / mbar |
20,0 / 0,3 |
20,0 / 0,3 |
20,0 / 0,3 |
20,0 / 0,3 |
|
Combustion air volume at nominal load |
m³/h |
79,0 |
84,0 |
93,0 |
93,0 |
|
Flue gas pipe diameter |
mm |
149 |
149 |
149 |
149 |
NL = Nominal load, PL = Partial load
- Energy efficiency labeling in accordance with VO (EU) 2015/1187 as a combined system of solid fuel boiler and temperature controller
- Pump output less water resistance in the boiler
- Detailed information on the fuel can be found in the operating instructions in the section entitled “Permitted fuels”
Technical data PE1e Pellet Condensing
Technical data PE1e Pellet Condensing |
45 |
50 |
55 |
60 |
L1 Boiler length |
1690 |
1690 |
1690 |
1690 |
L2 Total length |
1780 |
1780 |
1780 |
1780 |
B1 Boiler width |
730 |
730 |
730 |
730 |
B2 Boiler width incl. cover for electrostatic particle separator (optional) |
810 |
810 |
810 |
810 |
B3 Distance between flow connection and side of boiler |
590 |
590 |
590 |
590 |
B4 Distance between return connection and side of boiler |
510 |
510 |
510 |
510 |
B5 Distance between fresh water connection and side of boiler |
395 |
395 |
395 |
395 |
B6 Distance of supply air connection to side of boiler (optional) |
560 |
560 |
560 |
560 |
B7 Distance between flue gas pipe connection and side of boiler |
205 |
205 |
205 |
205 |
H1 Boiler height |
1620 |
1620 |
1620 |
1620 |
H2 Height of flow connection / fresh water |
1425 |
1425 |
1425 |
1425 |
H3 Height, return connection |
645 |
645 |
645 |
645 |
H4 Height of supply air connection (optional) |
100 |
100 |
100 |
100 |
H5 Height, flue pipe connection |
1025 |
1025 |
1025 |
1025 |
All information in mm!